Belden Store
28156A

Product Number: 28156A

TC VN/PVC, 3+G C #4+8 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 4+8AWG (7x12+7x16) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

28156A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCOrder
28156A 0105000BlackReel5,000 ft612825135593Order online
28156A 01010000BlackReel10,000 ft612825135586Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.386 Revision Date: 04-08-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC100A1041RA

Construction Details

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)347x12BC - Bare Copper
Ground187x16BC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.042 in (1.1 mm)
Nom. Insulation Diameter0.309 in (7.85 mm)
Color CodeBlack and Numbered

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.822 in (20.9 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.26 Ohm/1000ft95 Amps per Conductor at 30oC
Ground0.65 Ohm/1000ft (2.1 Ohm/km)55 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC-ER)

Mechanical Characteristics

Max. Pull Tension1877.4 lbs (851.57 kg)
Bulk Cable Weight605 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.3.28 in (83.3 mm)
Installation Min.4.1 in (100 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, THWN-2 Singles
European Directive ComplianceEU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.386 Revision Date: 04-08-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.