Belden Store
1038A

Product Number: 1038A

Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 50 Pair 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.526 in (38.76 mm)

Conductor

ElementPair(s)
No. of Elements50
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeBlack, White Numbered

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC
NotesExtra polyester tape for isolation

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.085 in (2.2 mm)
Nom. Diameter1.526 in (38.76 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementPair(s)
Nom. Conductor DCR5.86 Ohm/1000ft (19.2 Ohm/km)

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension2962 lbs (1344 kg)
Bulk Cable Weight1226.3 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30C to 90C Dry, 75C wet

Bend Radius

Stationary Min.15.3 in (389 mm)
Installation Min.15.3 in (389 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 (FT4 Loading), FT4, 1202
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.224 Revision Date: 01-04-2024

Resources

Related tray & tc cable