Belden Store
1039A

Product Number: 1039A

Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet

UL Instrumentation, 4 Pair 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

1039A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
1039A 0107500BlackReel7,500 ft612825105206C ZOrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.574 in (14.6 mm)

Conductor

ElementPair(s)
No. of Elements4
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeICEA Chart E1

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC
Noteseach pair

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.064 in (1.6 mm)
Nom. Diameter0.574 in (14.6 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR3.14 Ohm/1000ft (10.3 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR4.2 Ohm/1000ft
Nom. Inner Shield DCR5.49 Ohm/1000ft (18.0 Ohm/km)
Max. Current13 Amps per conductor @ 30°C

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension344 lbs (156 kg)
Bulk Cable Weight188 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to 90°C Dry/Wet

Bend Radius

Stationary Min.6.9 in (180 mm)
Installation Min.6.9 in (180 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 FT4 Loading, FT4, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)07-KA080011-MSHA

History

Update and RevisionRevision Number: 0.621 Revision Date: 04-10-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Resources