TC VN/PVC, 3+G C #6+8 Str BC, PVC-NYL Ins M4, LCS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 6+8AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Longitudinal Corrugated Copper Tape, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
- Orderable items
- 1
Part numbers
28153AC is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Putup Type | Order |
|---|---|---|
| 28153AC 0105000 | Reel | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.76 Revision Date: 02-20-2026 |
Product Overview
| Suitable Applications | Power and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.776 in |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 3 | 6 AWG | 7x14 | BC - Bare Copper |
| Ground Wire | 1 | 8 AWG | 7x16 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | PVC/Nylon - Polyvinyl Chloride + Nylon | 0.038 in (0.97 mm) | 0.254 in mm | Black and Numbered |
| Ground Wire | No Insulation |
Outer Shield
| Shield Type | Corrugated Tape |
|---|---|
| Material | Bare Copper (BC) |
| Coverage | 100% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.063 in (1.6 mm) |
| Nom. Diameter | 0.776 in |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 0.6 Ohm/1000ft (2.0 Ohm/km) |
|---|
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|---|---|
| Conductor(s) | 0.41 Ohm/1000ft | 75 Amps per Conductor at 30oC |
| Ground Wire | 0.67 Ohm/1000ft (2.2 Ohm/km) | 55 Amps per Conductor at 30oC |
Voltage
| UL Voltage Rating | 600 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 1480.5 lbs (671.54 kg) |
|---|---|
| Bulk Cable Weight | 410 lbs/1000ft |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | Wet/Dry: -30°C To +90°C |
Bend Radius
| Stationary Min. | 9.312 in (236.5 mm) |
|---|---|
| Installation Min. | 9.312 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
|---|---|
| Sustainability | CA Prop 65 |
| Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC-ER, THWN-2 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.76 Revision Date: 02-20-2026 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon