Belden Store
29721C

Product Number: 29721C

VFD, 3C #14 Str BC XLPE Ins + #14 Symm. Seg. Gnd (3 of #18) Str BC, CTS, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B

Belden Basics VFD, 3 Conductor 14AWG (7x22) Bare Copper XLPE Insulation M4 Color Code + 14AWG Symmetrical Segmented Ground (3 of 18AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

29721C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
29721C 0102500Reel612825445432Order online
29721C 0105000Reel612825445449Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.93 Revision Date: 04-01-2026

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements

Construction Details

Overall Cable Diameter (Nominal)0.566 in (14.4 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)314 AWG7x22BC - Bare CopperASTM B3 Copper B8 Class B Stranding
Ground318 AWG7x26BC - Bare CopperSegmented 14AWG Ground

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.063 in (1.6 mm)0.197 in (5.00 mm)Black and Numbered
GroundNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.566 in (14.4 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-ShieldNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Conductor(s)2.253 Ohm/1000ft (7.392 Ohm/km)21 pF/ft (69 pF/m)38 pF/ft (120 pF/m)38 pF/ft (120 pF/m)90 Ohm55%25 Amps per Conductor at 30oC
1.4 Ohm/1000ft (4.6 Ohm/km)

Voltage

UL Voltage Rating2000 V (TC), 1000 V (CSA AWM I/II A/B)

Mechanical Characteristics

Max. Pull Tension231 lbs (105 kg)
Bulk Cable Weight185 lbs/1000ft (275 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.6.8 in (170 mm)
Installation Min.6.8 in (170 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL ComplianceArticle 336, TC-ER, RHW-2
AWM ComplianceI/II A/B
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.93 Revision Date: 04-01-2026

Resources