Product Number: U042A4G

TC-ER XLPE/LSZH, 4+G C #2/0 Str BC, XLPE Ins M4, 1 #6 Grnd, Blk LSZH Jkt, 600V TC-ER 90C Dry/Wet SUN RES

UL Type TC (1277) XLPE/LSZH, 4+G Conductor 2/0 AWG (19x12) Bare Copper, XLPE Insulation M4 Color Code, 1 6AWG (7x16) Ground Wire, Black LSZH Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.54 Revision Date: 05-31-2024

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor Count4

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)2/019x11.5BC - Bare Copper4
Ground67x14BC - Bare Copper1

Insulation

MaterialNominal DiameterNominal Wall Thickness
XLP, XLPO, XLPE (Thermoset)0.521 in0.056 in
No Insulation

Color Chart

NumberConductors 1 - 4
ColorICEA S-73-732 Table M4: Black and Numbered

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
Nominal Diameter1.464 in
Nominal Wall Thickness0.103 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR.084 Ohm/1000ft

Current

Max. Recommended Current [A]156 Amps per Conductor at 30oC

Voltage

UL DescriptionTC
UL Voltage Rating600 V RMS (Type TC)
Voltage Rating [V]600 V RMS (Type TC)

Temperature Range

UL Temperature Rating90°C Dry, 90°C Wet
Operating Temperature Range-30°C To +90°C
Wet Temp Range-30°C To +90 °C

Mechanical Characteristics

Bulk Cable Weight1692 lbs/1000ft
Maximum Recommended Pulling Tension4260 lbs
Minimum Minor Axis Bend Radius7.32 in

Standards

NEC/(UL) ComplianceTC-ER, XHHW-2

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/11/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 Vertical Tray
IEEE Flammability1202
UL voltage rating600 V RMS (Type TC)

History

Update and RevisionRevision Number: 0.54 Revision Date: 05-31-2024

Resources