Belden Store
BeldenU03064C

Product Number: U03064C

TC-ER XLPE/LSZH, 3+G C #6 Str BC, XLPE Ins, M4, #10 Str BC Grnd, Blk LSZH Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR

UL Type TC-ER (1277) XLPE/LSZH, 3+G Conductor 6 AWG (7x14) Bare Copper, XLPE Insulation, M4 Color Code, 1 10 AWG (7x18) Bare Copper Ground Wire, Black LSZH Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

U03064C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
U03064C 0102500ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.57 Revision Date: 02-20-2026

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementSizeStrandingMaterial
Conductor(s)67x14BC - Bare Copper
Ground107x18BC - Bare Copper

Insulation

MaterialNom. ThicknessNom. Insulation DiameterColor Code
XLP, XLPO, XLPE (Thermoset)0.0465 in (1.18 mm)0.270 in (6.86 mm)ICEA S-73-732 Table M4: Black and Numbered
No Insulation

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.712 in

Electrical Characteristics

Electricals

Nom. Conductor DCR.41 Ohm/1000ft (1.3 Ohm/km)
Max. Current75 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V RMS (Type TC) (TC)

Mechanical Characteristics

Max. Pull Tension827 lbs (375 kg)
Bulk Cable Weight403 lbs/1000ft (600 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, 1202
NEC / UL ComplianceTC-ER, XHHW-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History