Belden Store
BeldenU02102

Product Number: U02102

TC XLPE/LSZH, 2 C #10 Str BC, XLPE Ins E2, Blk LSZH Jkt, 600V TC 90C Dry/Wet SUN RES

UL Type TC (1277) XLPE/LSZH, 2 Conductor 10 AWG (7x18) Bare Copper, XLPE Insulation E2 Color Code, Black LSZH Outer Jacket, 600V TC 90C Dry/Wet SUN RES

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.54 Revision Date: 05-31-2024

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor Count2

Conductor

ElementConductor(s)
AWG10
Stranding7x18
MaterialBC - Bare Copper
No. of Conductors2

Insulation

MaterialXLP, XLPO, XLPE (Thermoset)
Nominal Diameter0.174 in
Nominal Wall Thickness0.031 in

Color Chart

NumberColor
1Black
2Red

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
Nominal Diameter0.477 in
Nominal Wall Thickness0.067 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR1.04 Ohm/1000ft

Current

Max. Recommended Current [A]40 Amps per Conductor at 30oC

Voltage

UL DescriptionTC
UL Voltage Rating600 V RMS (Type TC)
Voltage Rating [V]600 V RMS (Type TC)

Temperature Range

UL Temperature Rating90°C Dry, 90°C Wet
Operating Temperature Range-30°C To +90°C
Wet Temp Range-30°C To +90 °C

Mechanical Characteristics

Bulk Cable Weight138 lbs/1000ft
Maximum Recommended Pulling Tension166 lbs
Minimum Minor Axis Bend Radius1.91 in

Standards

NEC/(UL) ComplianceTC, XHHW-2

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/11/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 UL Loading
IEEE Flammability1202
UL voltage rating600 V RMS (Type TC)

History

Update and RevisionRevision Number: 0.54 Revision Date: 05-31-2024

Resources

Related tray & tc cable