Belden Store
BeldenO02121X

Product Number: O02121X

TC EPR(EPCV)/CPE, 2+G C #12+12 Str BC, EPR(EPCV) Ins E1, Blk CPE Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) EPR(EPCV)/CPE, 2+G Conductor 12+12AWG (Class B) Bare Copper, EPR(EPCV) Insulation E1 Color Code, Black CPE Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 1000V

Construction Details

Overall Cable Diameter (Nominal)0.419 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)212 AWG7x20BC - Bare Copper
Ground Wire112 AWG7x20BC - Bare Copper

Insulation

ElementSeparatorMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)Conductor(s)XLPO - Crosslink Polyolefin0.031 in (0.79 mm)0.151 in (3.84 mm)Black, White
Ground WireXLPO - Crosslink Polyolefin0.031 in (0.79 mm)0.151 in (3.84 mm)Green

Inner Shield

Shield TypeNo Shield

Outer Shield

Shield TypeNo Shield

Outer Jacket

MaterialCPE - Chlorinated Polyethylene
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.419 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.68 Ohm/1000ft30 Amps per Conductor at 30oC
Ground Wire1.72 Ohm/1000ft (5.64 Ohm/km)30 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER)

Mechanical Characteristics

Max. Pull Tension260 lbs (120 kg)
Bulk Cable Weight123 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.1.676 in (42.57 mm)
Installation Min.2.095 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, XHHW-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)