Belden Store
BeldenO02101X

Product Number: O02101X

TC EPR(EPCV)/CPE, 2+G C #10+10 Str BC, EPR(EPCV) Ins E1, Blk CPE Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) EPR(EPCV)/CPE, 2+G Conductor 10+10AWG (Class B) Bare Copper, EPR(EPCV) Insulation E1 Color Code, Black CPE Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

O02101X is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
O02101X 0105000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.61 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 1000V

Construction Details

Overall Cable Diameter (Nominal)0.486 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)210 AWG7x18BC - Bare Copper
Ground Wire110 AWG7x18BC - Bare Copper

Insulation

ElementSeparatorMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)Conductor(s)XLPO - Crosslink Polyolefin0.032 in (0.81 mm)0.182 in (4.62 mm)Black, White
Ground WireXLPO - Crosslink Polyolefin0.032 in (0.81 mm)0.182 in (4.62 mm)Green

Inner Shield

Shield TypeNo Shield

Outer Shield

Shield TypeNo Shield

Outer Jacket

MaterialCPE - Chlorinated Polyethylene
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.486 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.06 Ohm/1000ft40 Amps per Conductor at 30oC
Ground Wire1.080 Ohm/1000ft (3.543 Ohm/km)

Voltage

UL Voltage Rating600 V (TC-ER)

Mechanical Characteristics

Max. Pull Tension440.4 lbs (199.8 kg)
Bulk Cable Weight123 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.1.944 in (49.38 mm)
Installation Min.2.43 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, XHHW-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.61 Revision Date: 02-20-2026

Resources