Belden Store
BeldenA03162R

Product Number: A03162R

TC VN/PVC, 3 C #16 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3 Conductor 16AWG (7x24) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

A03162R is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
A03162R 0105000ReelOrder online
A03162R01010000ReelOrder online
A03162R01015000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.62 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.312 in

Conductor

ElementConductor(s)
No. of Elements3
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in mm
Color CodeBlack, Red, Blue

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.312 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.2 Ohm/1000ft
Max. Current18 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V RMS (NPLF) (NPLF)

Mechanical Characteristics

Max. Pull Tension107 lbs (48.5 kg)
Bulk Cable Weight68 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to 90°C Dry/Wet

Bend Radius

Stationary Min.1.248 in (31.70 mm)
Installation Min.1.56 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, TFFN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)