Belden Store
BeldenA03122J

Product Number: A03122J

TC VN/PVC, 3+G C #12+12 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 12+12AWG (7x20) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

A03122J is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
A03122J 0105000ReelOrder online
A03122J01010000ReelOrder online
A03122J01020000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.65 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.408 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)312 AWG7x20BC - Bare Copper
Ground Wire112 AWG7x20BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.019 in (0.48 mm)0.131 in (3.33 mm)ICEA Chart E2
Ground WirePVC/Nylon - Polyvinyl Chloride + Nylon0.019 in (0.48 mm)0.131 in (3.33 mm)Green

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.408 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.72 Ohm/1000ft30 Amps per Conductor at 30oC
Ground Wire1.72 Ohm/1000ft (5.64 Ohm/km)30 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension347.2 lbs (157.5 kg)
Bulk Cable Weight136 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C Wet/90°C Dry

Bend Radius

Stationary Min.1.63 in (41.4 mm)
Installation Min.2.04 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 310, Article 336, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.65 Revision Date: 02-20-2026

Resources

Related tray & tc cable