TC VN/PVC, 3 C #12 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
UL Type TC (1277) PVC-Nylon/PVC, 3 Conductor 12AWG (Class B) Bare Copper, PVC-NYL Insulation E1 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
- Orderable items
- 1
Part numbers
A03121W is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Put-Up Type | Order |
|---|---|---|
| A03121W 0105000 | Reel | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.50 Revision Date: 04-02-2026 |
Physical Characteristics (Overall)
| Conductor Count | 3 |
|---|
Conductor
| Element | Conductor(s) |
|---|---|
| AWG | 12 |
| Stranding | 7x20 |
| Material | BC - Bare Copper |
| No. of Conductors | 3 |
Insulation
| Material | PVC/Nylon - Polyvinyl Chloride + Nylon |
|---|---|
| Nominal Diameter | 0.131 in |
Color Chart
| Number | Color |
|---|---|
| 1 | Black |
| 2 | White |
| 3 | Red |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nominal Diameter | 0.385 in |
| Nominal Wall Thickness | 0.047 in |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | 1.65 Ohm/1000ft |
|---|
Current
| Max. Recommended Current [A] | 30 Amps per Conductor at 30oC |
|---|
Voltage
| UL Description | TC |
|---|---|
| UL Voltage Rating | 600 V RMS (Type TC) |
| Voltage Rating [V] | 600 V RMS (Type TC) |
Temperature Range
| UL Temperature Rating | 90°C Dry, 75°C Wet |
|---|---|
| Operating Temperature Range | -25°C To +90°C |
Mechanical Characteristics
| UV Resistance | Yes |
|---|---|
| Min Bend Radius (Overall) | 3.85 in |
| Minimum Minor Axis Bend Radius | 1.54 in |
Standards
| NEC/(UL) Compliance | TC-ER, NPLF, THWN-2 |
|---|
Applicable Environmental and Other Programs
| EU Directive 2000/53/EC (ELV) | Yes |
|---|---|
| EU Directive 2011/65/EU (RoHS 2) | Yes |
| EU Directive 2012/19/EU (WEEE) | Yes |
| EU Directive 2015/863/EU (RoHS 2 amendment) | Yes |
| EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
| EU CE Mark | Yes |
Suitability
| Suitability - Burial | Yes |
|---|---|
| Suitability - Indoor | Yes |
| Suitability - Outdoor | Yes |
| Suitability - Sunlight Resistance | Yes |
Flammability, LS0H, Toxicity Testing
| UL Flammability | UL1685 Vertical Tray Flame Test |
|---|---|
| IEEE Flammability | IEEE 1202 |
| UL voltage rating | 600 V RMS (Type TC) |
History
| Update and Revision | Revision Number: 0.50 Revision Date: 04-02-2026 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon