Belden Store
BeldenA03102Q

Product Number: A03102Q

TC VN/PVC, 3 C #10 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3 Conductor 10AWG (7x18) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.49 Revision Date: 01-10-2024

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor Count3

Conductor

ElementConductor(s)
AWG10
Stranding7x18
MaterialBC - Bare Copper
Nominal Diameter0.110 in
No. of Conductors3

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nominal Diameter0.164 in

Color Chart

NumberColor
1Black
2Red
3Blue

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.450 in
Nominal Wall Thickness0.047 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR1.04 Ohm/1000ft

Current

Max. Recommended Current [A]40 Amps per Conductor at 30oC

Voltage

UL DescriptionTC
UL Voltage Rating600 V RMS (Type TC)
Voltage Rating [V]600 V RMS (Type TC)

Temperature Range

UL Temperature Rating90°C Dry, 75°C Wet
Operating Temperature Range-25°C To +90°C

Mechanical Characteristics

UV ResistanceYes
Min Bend Radius (Overall)4.5 in
Minimum Minor Axis Bend Radius1.80 in

Standards

NEC/(UL) ComplianceTC-ER

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 Vertical Tray Flame Test
UL voltage rating600 V RMS (Type TC)

History

Update and RevisionRevision Number: 0.49 Revision Date: 01-10-2024

Resources

Related tray & tc cable