TC VN/PVC, 3+G C #4+8 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry 75C Wet SUN RES DIR BUR
UL Type TC-ER (1277) PVC-Nylon/PVC, 3+G Conductor 4+8AWG (7x12+7x16) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry 75C Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.50 Revision Date: 05-31-2024 |
Product Overview
| Suitable Applications | harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
|---|
Physical Characteristics (Overall)
| Conductor Count | 3 |
|---|
Conductor
| Element | AWG | Stranding | Material | No. of Conductors |
|---|---|---|---|---|
| Conductor(s) | 4 | 7x12 | BC - Bare Copper | 3 |
| Ground | 8 | 7x16 | BC - Bare Copper | 1 |
Insulation
| Material | Nominal Diameter | Nominal Wall Thickness |
|---|---|---|
| PVC/Nylon - Polyvinyl Chloride + Nylon | 0.0309 in | 0.0485 in |
| No Insulation |
Color Chart
| Number | Color |
|---|---|
| 1 | Black |
| 2 | Red |
| 3 | Blue |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nominal Diameter | 0.822 in |
| Nominal Wall Thickness | 0.063 in |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | 0.26 Ohm/1000ft |
|---|
Current
| Max. Recommended Current [A] | 95 Amps per Conductor at 30oC |
|---|
Voltage
| UL Description | TC-ER |
|---|---|
| UL Voltage Rating | 600 V RMS (Type TC) |
| Voltage Rating [V] | 600 V RMS (Type TC) |
Temperature Range
| Operating Temperature Range | -30°C to 90°C Dry, +75°C Wet |
|---|
Mechanical Characteristics
| Bulk Cable Weight | 548 lbs/1000ft |
|---|---|
| Maximum Recommended Pulling Tension | 1002 lbs |
| Minimum Minor Axis Bend Radius | 3.29 in |
Standards
| NEC/(UL) Compliance | TC-ER, THWN-2 Singles |
|---|
Applicable Environmental and Other Programs
| EU Directive 2000/53/EC (ELV) | Yes |
|---|---|
| EU Directive 2011/65/EU (RoHS 2) | Yes |
| EU Directive 2012/19/EU (WEEE) | Yes |
| EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
Suitability
| Suitability - Burial | Yes |
|---|---|
| Suitability - Indoor | Yes |
| Suitability - Outdoor | Yes |
| Suitability - Sunlight Resistance | Yes |
Flammability, LS0H, Toxicity Testing
| UL Flammability | UL1685 UL Loading |
|---|---|
| IEEE Flammability | 1202 |
| UL voltage rating | 600 V RMS (Type TC) |
History
| Update and Revision | Revision Number: 0.50 Revision Date: 05-31-2024 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon