Belden Store
BeldenA0214KO

Product Number: A0214KO

TC-ER VN/PVC, 2+G C #14 Str BC, PVC-NYL Ins, E2, 1 C #14 Str BC Ins Grnd, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

UL Type TC-ER (1277) PVC-Nylon/PVC, 2+G Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, 1 Conductor 14 (7x22) Bare Copper Insulated Ground, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.53 Revision Date: 05-31-2024

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Physical Characteristics (Overall)

Conductor Count2

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)147x22BC - Bare Copper2
Ground147x22BC - Bare Copper1

Insulation

MaterialNominal DiameterNominal Wall Thickness
PVC/Nylon - Polyvinyl Chloride + Nylon0.116 in0.024 in
PVC/Nylon - Polyvinyl Chloride + Nylon0.0116 in0.024 in

Color Chart

NumberColor
1Black
2Red
GroundGreen

Outer Shield

TypeTape
MaterialBi-Laminate (Alum+Poly)
Material Trade NameBeldfoil®
Coverage [%]100%
Drainwire MaterialTC - Tinned Copper
Drainwire AWG14

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.348 in
Nominal Wall Thickness0.047 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR2.52 Ohm/1000ft

Current

Max. Recommended Current [A]25 Amps per Conductor at 30oC

Voltage

DescriptionUL DescriptionUL Voltage RatingVoltage Rating [V]
Type TCTC600 V RMS600 V RMS
NPLF150 V RMS

Temperature Range

UL Temperature Rating90°C Wet/Dry
Operating Temperature Range'-30°C To +90°C

Mechanical Characteristics

UV ResistanceYes
Bulk Cable Weight89 lbs/1000ft
Maximum Recommended Pulling Tension64 lbs
Minimum Minor Axis Bend Radius3.48 in

Standards

NEC ArticlesArticle 336
NEC/(UL) ComplianceNPLF, TC-ER, THHN/THWN Singles

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/11/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceYes
EU CE MarkYes

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL 1685 UL Loading
IEEE Flammability1202
UL voltage rating600 V RMS (Type TC)

Plenum/Non-Plenum

Plenum (Y/N)No

History

Update and RevisionRevision Number: 0.53 Revision Date: 05-31-2024

Resources

Related tray & tc cable