TC VN/PVC, 2 C #12 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 2 Conductor 12AWG (7x20) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

A0212KR is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
A0212KR 0105000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.63 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.424 in

Conductor

ElementConductor(s)
No. of Elements2
Size12 AWG
Stranding7x20
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.019 in (0.48 mm)
Nom. Insulation Diameter0.131 in (3.33 mm)
Color CodeICEA Chart E2

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type14 AWG (7x22) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.424 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR2.27 Ohm/1000ft (7.45 Ohm/km)

Electricals

Nom. Conductor DCR1.72 Ohm/1000ft
Max. Current30 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension260.4 lbs (118.1 kg)
Bulk Cable Weight105 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C Wet/90°C Dry

Bend Radius

Stationary Min.1.69 in (42.9 mm)
Installation Min.2.12 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 310, Article 336, TC, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)