TC VN/PVC, 2 C #8 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR
UL Type TC (1277) PVC-Nylon/PVC, 2 Conductor 8AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC 90C Dry/Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
A02084R is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Putup Type | Order |
|---|---|---|
| A02084R 0105000 | Reel | Order online |
| A02084R01010000 | Reel | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.64 Revision Date: 02-20-2026 |
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.562 in |
|---|
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 2 |
| Size | 8 AWG |
| Stranding | 7x16 |
| Material | BC - Bare Copper |
Insulation
| Element | Conductor(s) |
|---|---|
| Material | PVC/Nylon - Polyvinyl Chloride + Nylon |
| Nom. Thickness | 0.038 in (0.97 mm) |
| Nom. Insulation Diameter | 0.218 in mm |
| Color Code | Black and Numbered |
Outer Shield
| Material | No Shield |
|---|
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.063 in (1.6 mm) |
| Nom. Diameter | 0.562 in |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | 0.666 Ohm/1000ft |
|---|---|
| Max. Current | 55 Amps per Conductor at 30oC |
Voltage
| UL Voltage Rating | 600 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 436.8 |
|---|---|
| Bulk Cable Weight | 549 lbs/1000ft |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -25°C To +90°C |
Bend Radius
| Stationary Min. | 2.248 in (57.10 mm) |
|---|---|
| Installation Min. | 2.81 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
|---|---|
| Sustainability | CA Prop 65 |
| Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC, THWN-2 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.64 Revision Date: 02-20-2026 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon