Product Number: 62T1812

Inst, 12 Tri #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 12 Triad 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.37 Revision Date: 05-31-2024

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Overall Cable Diameter (Nominal)0.947 in

Conductor

ElementTriad(s)
No. of Elements12
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementTriad(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeBlack & White & Red and Numbered, [deleted]

Inner Shield

ElementTriad(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type22 AWG (7x30) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type22 AWG (7x30) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.947 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR6.6 Ohm/1000ft
Nom. Inner Shield DCR12.3 Ohm/1000ft (40.4 Ohm/km)
Max. Current6 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension656 lbs (298 kg)
Bulk Cable Weight446 lbs/1000ft

Temperature

UL TemperatureUL: 75°C Wet, 90°C Dry; NPLF: 90°C
Operating-20°C to +90°C Dry, +75°C Wet

Bend Radius

Stationary Min.11.364 in (288.65 mm)
Installation Min.11.364 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesTriad groups are numbered for ease of identification. Alternate color coding available upon request.