Belden Store
Belden62T1802

Product Number: 62T1802

TC VN/PVC, 2 Tri #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) VN/PVC, 2 Triad 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

62T1802 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
62T1802 0102500ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.55 Revision Date: 02-03-2025

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS), programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Conductor

ElementPair(s)
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Insulation Diameter0.087 in (2.2 mm)
Color CodeBlack, White & Red and Numbered 1, Black, White & Red and Numbered 2

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.473 in (12.0 mm)

Electrical Characteristics

Electricals

Nom. Conductor DCR7.06 Ohm/1000ft
Nom. Inner Shield DCR0.97 Ohm/1000ft (3.2 Ohm/km)
Max. Current5.6 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V, 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension134.4 lbs (60.96 kg)
Bulk Cable Weight97 lbs/1000ft

Temperature

UL Temperature75°C Wet, 90°C Dry
Operating-30°C To +90°C

Standards and Compliance

Environmental SuitabilityOutdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, FT4, IEEE 1202
NEC / UL ComplianceTC-ER, NPLF
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.55 Revision Date: 02-03-2025

Resources

Related tray & tc cable