Belden Store
Belden62T1604

Product Number: 62T1604

Inst, 4 Tri #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 4 Triad 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

62T1604 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
62T1604 0105000Reel612825359890Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.47 Revision Date: 09-07-2025

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Overall Cable Diameter (Nominal)0.647 in

Conductor

ElementTriad(s)
No. of Elements4
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementTriad(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeBlack & White & Red and Numbered

Inner Shield

ElementTriad(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.647 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR6.7 Ohm/1000ft (22 Ohm/km)

Electricals

Nom. Conductor DCR4.2 Ohm/1000ft
Nom. Inner Shield DCR8.0 Ohm/1000ft (26 Ohm/km)
Max. Current9 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension348 lbs (158 kg)
Bulk Cable Weight227 lbs/1000ft

Temperature

UL TemperatureUL: 75°C Wet, 90°C Dry; NPLF: 90°C
Operating-20°C to +90°C Dry, +75°C Wet

Bend Radius

Stationary Min.7.764 in (197.2 mm)
Installation Min.7.764 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlternate color coding available upon request.

History

Update and RevisionRevision Number: 0.47 Revision Date: 09-07-2025

Resources

Related tray & tc cable