Belden Store
Belden62T1602

Product Number: 62T1602

Inst, 2 Tri #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 2 Triad 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.44 Revision Date: 11-21-2024

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Overall Cable Diameter (Nominal)0.559 in

Conductor

ElementTriad(s)
No. of Elements2
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementTriad(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.0101 in (0.257 mm)
Color CodeICEA Chart E1

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.559 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.2 Ohm/1000ft
Nom. Inner Shield DCR8.4 Ohm/1000ft (28 Ohm/km)
Max. Current15 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension252 lbs (114 kg)
Bulk Cable Weight140 lbs/1000ft

Temperature

UL TemperatureUL: 90°C Dry, 75°C Wet; NPLF: 90°C
Operating-20°C To +90°C Dry, +75°C Wet

Bend Radius

Stationary Min.6.708 in (170.4 mm)
Installation Min.6.708 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.44 Revision Date: 11-21-2024

Resources

Related tray & tc cable