Belden Store
62P1612

Product Number: 62P1612

Inst PVC/PVC, 12 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, TC-ER NPLF 90C Dry 75C Wet

UL Instrumentation, 12 Pair 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, TC-ER NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

62P1612 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
62P1612 0102500Reel612825363651Order online
62P1612 0105000Reel612825359524Order online
62P161201010000Reel—Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.198 Revision Date: 04-10-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Conductor

ElementPair(s)
No. of Elements12
Size16
Stranding7x24
MaterialBC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeICEA Chart E1

Inner Shield

ElementEach Pair
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.935 in (23.7 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR1.3 Ohm/1000ft (4.3 Ohm/km)

Electricals

Nom. Conductor DCR4.26 Ohm/1000ft (14.0 Ohm/km)
Nom. Inner Shield DCR1.33 Ohm/1000ft (4.36 Ohm/km)
Max. Current8 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension1020 lbs (463 kg)
Bulk Cable Weight468 lbs/1000ft (696 kg/km)

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C To +90°C Dry, +75°C Wet
Installation-25°C To +90°C

Bend Radius

Stationary Min.3.72 in (94.5 mm)
Installation Min.4.65 in (118 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER, TFFN
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.198 Revision Date: 04-10-2026

Resources