Belden Store
Belden61T1801

Product Number: 61T1801

Inst, 1 Tri #18 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 1 Triad 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

61T1801 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
61T180101010000Reel612825360261Order online
61T1801 0105000Reel612825434733Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.101 Revision Date: 09-07-2025

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Overall Cable Diameter (Nominal)0.288 in

Conductor

ElementConductor(s)
No. of Elements3
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeICEA Chart E1

Inner Shield

Shield TypeNo Shield

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type22 AWG (7x30) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.288 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR7.46 Ohm/1000ft (24.5 Ohm/km)

Electricals

Nom. Conductor DCR6.7 Ohm/1000ft
Max. Current15 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension81 lbs (37 kg)
Bulk Cable Weight42 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-20°C To +90°C Dry, +75°C Wet

Bend Radius

Stationary Min.3.456 in (87.78 mm)
Installation Min.3.456 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlternate color coding available upon request.

History

Update and RevisionRevision Number: 0.101 Revision Date: 09-07-2025

Resources

Related tray & tc cable