Belden Store
Belden61T1608

Product Number: 61T1608

Inst, 8 Tri #16 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 8 Triad 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

61T1608 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
61T1608 0104350ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.38 Revision Date: 09-07-2025

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control

Construction Details

Overall Cable Diameter (Nominal)0.826 in

Conductor

ElementTriad(s)
No. of Elements8
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementTriad(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeICEA S-73-732 Table E1: Black & White & Red and Numbered

Inner Shield

MaterialNo Shield

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.826 in

Electrical Characteristics

Nom Outer Shield DCR6.14 Ohm/1000ft (20.1 Ohm/km)

Electricals

Nom. Conductor DCR4.2 Ohm/1000ft
Max. Current8 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension869 lbs (394 kg)
Bulk Cable Weight363 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C To +90 °C Dry, +75°C Wet

Bend Radius

Stationary Min.9.912 in (251.8 mm)
Installation Min.9.912 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlternate color coding available upon request.

History

Update and RevisionRevision Number: 0.38 Revision Date: 09-07-2025

Resources