Belden Store
Belden48643AZ

Product Number: 48643AZ

TC VN/PVC, 2+G C #10+10 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 2+G Conductor 10+10AWG (7x18) Bare Copper, PVC-NYL Insulation E1 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

48643AZ is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
48643AZ 0105000Reel612825336280Order online
48643AZ01010000Reel612825336297Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.68 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.451 in (11.5 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)210 AWG7x18BC - Bare Copper
Ground Wire110 AWG7x18BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.028 in (0.71 mm)0.166 in mmBlack, White, Green
Ground WirePVC/Nylon - Polyvinyl Chloride + Nylon0.028 in (0.71 mm)0.166 in inGreen

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.451 in (11.5 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.04 Ohm/1000ft40 Amps per Conductor at 30oC
Ground Wire1.08 Ohm/1000ft (3.54 Ohm/km)42 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension470.4 lbs (213.4 kg)
Bulk Cable Weight162 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C To +90°C

Bend Radius

Stationary Min.1.804 in (45.82 mm)
Installation Min.2.255 in (57.28 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.68 Revision Date: 02-20-2026

Resources

Related tray & tc cable