Belden Store
Belden48339A

Product Number: 48339A

TC VN/PVC, 5 C #16 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 5 Conductor 16AWG (Class B) Bare Copper, PVC-NYL Insulation E1 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.359 in

Conductor

ElementConductor(s)
No. of Elements5
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.020 in (0.51 mm)
Nom. Insulation Diameter0.099 in (2.5 mm)
Color CodeICEA Chart E1

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.359 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.2 Ohm/1000ft
Max. Current14.4 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension178.5 lbs (80.97 kg)
Bulk Cable Weight85 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C Wet/90°C Dry

Bend Radius

Stationary Min.1.43 in (36.3 mm)
Installation Min.1.79 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 400, Article 760, TC-ER, NPLF, TFFN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.55 Revision Date: 05-31-2024