Belden Store
Belden48112A

Product Number: 48112A

TC VN/PVC, 5 C #12 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 5 Conductor 12AWG (7x20) Bare Copper, PVC-NYL Insulation E1 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

48112A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
48112A 0105000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.48 Revision Date: 02-20-2026

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementConductor(s)
Size12
Stranding7x20
MaterialBC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Insulation Diameter0.131 in (3.33 mm)
Color CodeBlack, White, Red, Green, Orange

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.455 in

Electrical Characteristics

Electricals

Nom. Conductor DCR1.65 Ohm/1000ft (5.41 Ohm/km)
Max. Current24 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V RMS (Type TC) (TC-ER)

Mechanical Characteristics

Max. Pull Tension256 lbs (116 kg)
Bulk Cable Weight163 lbs/1000ft (243 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202
NEC / UL ComplianceTC-ER, THHN, THWN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.48 Revision Date: 02-20-2026