Belden Store
3103A

Product Number: 3103A

Inst, 1 Pr #12 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC 150V NPLF THHN OR THWN

UL Instrumentation, 1 Pair 12AWG (7x20) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF THHN OR THWN 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, actuators, positioners

Construction Details

Overall Cable Diameter (Nominal)0.364 in

Conductor

ElementConductor(s)
No. of Elements2
Size12 AWG
Stranding7x20
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.019 in (0.48 mm)
Nom. Insulation Diameter0.131 in (3.33 mm)
Color CodeBlack, White

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.364 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR1.65 Ohm/1000ft
Nom. Capacitance Cond-to-Cond56 pF/ft (180 pF/m)
Nom. Capacitance Cond-to-Shield106 pF/ft (348 pF/m)
Max. Current31 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension228 lbs (103 kg)
Bulk Cable Weight91 lbs/1000ft

Temperature

UL Temperature90°C Dry/Wet
Operating-25°C to +90°C

Bend Radius

Stationary Min.4.368 in (110.9 mm)
Installation Min.4.368 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, T-29-520, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlternate color coding available upon request.

History

Update and RevisionRevision Number: 0.272 Revision Date: 05-31-2024

Resources

Related tray & tc cable