Belden Store
3088A

Product Number: 3088A

Inst, 1 Pr #18 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry/Wet

UL Instrumentation, 1 Pair 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

3088A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCOrder
3088A 01010000BlackReel10,000 ft612825141099Order online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.276 in (7.01 mm)

Conductor

ElementPair(s)
No. of Elements1
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeBlack, White

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.276 in (7.01 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR8.49 Ohm/1000ft (27.9 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR7.06 Ohm/1000ft
Nom. Capacitance Cond-to-Cond41.3 pF/ft (135 pF/m)
Nom. Capacitance Cond-to-Shield74.3 pF/ft (244 pF/m)
Nom. Inductance0.1945 μH/ft (0.6381 μH/m)
Max. Current5 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension57 lbs (26 kg)
Bulk Cable Weight37 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to +90°C Dry, 75°C wet

Bend Radius

Stationary Min.2.8 in (71 mm)
Installation Min.2.8 in (71 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, T-29-520, IEEE 1202, FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.602 Revision Date: 04-10-2026

Resources

Related tray & tc cable