Belden Store
Belden3081A

Product Number: 3081A

Inst, 1 Tri #14 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF THHN OR THWN

UL Instrumentation, 1 Triad 14AWG (7x22) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF THHN OR THWN-2 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, actuators, positioners

Construction Details

Overall Cable Diameter (Nominal)0.359 in

Conductor

ElementConductor(s)
No. of Elements3
Size14 AWG
Stranding7x22
MaterialBC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.0225 in (0.572 mm)0.116 in (2.95 mm)Red, White, Black
Black & White & Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.359 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR2.3 Ohm/1000ft
Nom. Capacitance Cond-to-Cond57 pF/ft (190 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)102 pF/ft (335 pF/m)
Max. Current26 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight85 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-20°C to +90°C

Bend Radius

Stationary Min.4.308 in (109.4 mm)
Installation Min.4.308 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, T-29-520, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER, THWN-2
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlternate color coding available upon request.

History

Update and RevisionRevision Number: 0.459 Revision Date: 12-20-2024

Resources

Related tray & tc cable