Inst, 1 Tri #14 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF THHN OR THWN
UL Instrumentation, 1 Triad 14AWG (7x22) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF THHN OR THWN-2 90C Dry/Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
Specifications
Product Overview
| Suitable Applications | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, actuators, positioners |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.359 in |
|---|
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 3 |
| Size | 14 AWG |
| Stranding | 7x22 |
| Material | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | PVC/Nylon - Polyvinyl Chloride + Nylon | 0.0225 in (0.572 mm) | 0.116 in (2.95 mm) | Red, White, Black |
| Black & White & Red |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
| Drainwire Type | 16 AWG (7x24) TC |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.047 in (1.2 mm) |
| Nom. Diameter | 0.359 in |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | 2.3 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 57 pF/ft (190 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 102 pF/ft (335 pF/m) |
| Max. Current | 26 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 200 lbs (91 kg) |
|---|---|
| Bulk Cable Weight | 85 lbs/1000ft |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -20°C to +90°C |
Bend Radius
| Stationary Min. | 4.308 in (109.4 mm) |
|---|---|
| Installation Min. | 4.308 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| Flammability / Reaction to Fire | UL1685 UL Loading, T-29-520, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, Article 760, NPLF, TC-ER, THWN-2 |
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
Product Notes
| Notes | Alternate color coding available upon request. |
|---|
History
| Update and Revision | Revision Number: 0.459 Revision Date: 12-20-2024 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon