Belden Store
3080A

Product Number: 3080A

Inst, 1 Pr #14 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC 150V NPLF THHN OR THWN

UL Instrumentation, 1 Pair 14AWG (7x22) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF THHN OR THWN 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.320 in (8.13 mm)

Conductor

ElementPair(s)
No. of Elements1
Size14 AWG
Stranding7x22
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.024 in (0.61 mm)
Nom. Insulation Diameter0.116 in (2.95 mm)
Color CodeBlack, White

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.320 in (8.13 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementPair(s)
Nom. Conductor DCR2.6 Ohm/1000ft
Nom. Capacitance Cond-to-Cond48 pF/ft (160 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)102 pF/ft (335 pF/m)
Max. Current8 Amps per conductor at 25°C

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight65 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C to +90°C Dry, 75°C wet

Bend Radius

Stationary Min.3.9 in (99 mm)
Installation Min.3.9 in (99 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202, FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC, THHN, THWN
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.511 Revision Date: 12-20-2024

Resources

Related tray & tc cable