Belden Store
28627A

Product Number: 28627A

TC VN/PVC, 37 C #16 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 37 Conductor 16AWG (7x24) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
4

Ships from and sold by A5 IT.

Part numbers

28627A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
28627A 01010000Reel612825331032Order online
28627A 01010000Reel612825331032Order online
28627A 0105000Reel612825136347Order online
28627A 0105000Reel612825136347Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.369 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC100A1041RA

Construction Details

Overall Cable Diameter (Nominal)0.812 in (20.6 mm)

Conductor

ElementConductor(s)
No. of Elements37
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.020 in (0.51 mm)
Nom. Insulation Diameter0.099 in (2.5 mm)
Color CodeBlack, Red, Blue, Orange, Yellow, Brown, Red/Black, Blue/Black, Orange/Black, Yellow/Black, Brown/Black, Black/Red, Blue/Red, Orange/Red, Yellow/Red, Brown/Red, Black/Blue, Red/Blue, Orange/Blue, Yellow/Blue, Brown/Blue, Black/Orange, Red/Orange, Blue/Orange, Yellow/Orange, Brown/Orange, Black/Yellow, Red/Yellow, Blue/Yellow, Orange/Yellow, Brown/Yellow, Black/Brown, Red/Brown, Blue/Brown, Orange/Brown, Yellow/Brown, Black and Numbered

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.812 in (20.6 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.45 Ohm/1000ft
Max. Current7.2 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension1320.9 lbs (599.15 kg)
Bulk Cable Weight498 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.3.248 in (82.50 mm)
Installation Min.4.06 in (103 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 760, Article 336, Article 402, TC-ER, NPLF, TFFN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.369 Revision Date: 02-20-2026

Resources

Related tray & tc cable