Belden Store
28341AS

Product Number: 28341AS

TC VN/PVC, 12 C #16 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 12 Conductor 16AWG (7x24) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.509 in (12.9 mm)

Conductor

ElementConductor(s)
No. of Elements12
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.056 in (1.4 mm)
Nom. Insulation Diameter0.099 in (2.5 mm)
Color CodeBlack, Red, Blue, Orange, Yellow

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.509 in (12.9 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.45 Ohm/1000ft
Max. Current9 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension464.1 lbs (210.5 kg)
Bulk Cable Weight185 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet

Bend Radius

Stationary Min.6.108 in (155.1 mm)
Installation Min.6.108 in (155.1 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 402, TC-ER, TFFN

History

Update and RevisionRevision Number: 0.207 Revision Date: 04-08-2026