Belden Store
28327AS

Product Number: 28327AS

TC VN/PVC, 7 C #18 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 7 Conductor 18AWG (7x26) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

28327AS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
28327AS 0105000BlackReel5,000 ft612825135852C ZOrder online
28327AS01010000BlackReel10,000 ft612825135869C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.203 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)0.364 in

Conductor

ElementConductor(s)
No. of Elements7
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeBlack, Red, Blue, Orange, Yellow, Brown, Red/Black

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.364 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR4.7 Ohm/1000ft (15 Ohm/km)

Electricals

Nom. Conductor DCR6.7 Ohm/1000ft
Max. Current9.8 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension174 lbs (78.9 kg)
Bulk Cable Weight89 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.4.368 in (110.9 mm)
Installation Min.4.368 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 400, Article 760, TC-ER, NPLF, TFFN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.203 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Resources