Belden Store
28172A

Product Number: 28172A

TC VN/PVC, 4+G C #2/0 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 4+G Conductor 2/0AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

28172A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
28172A 0102500ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.184 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC200A1741RA

Construction Details

Overall Cable Diameter (Nominal)1.435 in (36.45 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)42/0 AWG19x11BC - Bare Copper
Ground Wire16 AWG7x14BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.062 in (1.6 mm)0.526 in mmBlack and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.435 in (36.45 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.084 Ohm/1000ft156 Amps per Conductor at 30oC
Ground Wire0.42 Ohm/1000ft (1.4 Ohm/km)75 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension6844.7 lbs (3104.7 kg)
Bulk Cable Weight2188 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C To +90°C

Bend Radius

Stationary Min.7.175 in (182.2 mm)
Installation Min.8.61 in (219 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC, THHN, THWN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.184 Revision Date: 02-20-2026

Resources

Related tray & tc cable