Belden Store
28161A

Product Number: 28161A

TC VN/PVC, 3+G C #1+6 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 1+6AWG (19x14+7x14H) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

28161A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCOrder
28161A 0105000BlackReel5,000 ft612825135654Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.484 Revision Date: 04-08-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC125A1271RA

Construction Details

Overall Cable Diameter (Nominal)1.125 in (28.58 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)31 AWG19x14BC - Bare Copper
Ground Wire16 AWG7x14BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.057 in (1.4 mm)0.445 in (11.3 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.125 in (28.58 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.13 Ohm/1000ft145 Amps per Conductor at 30oC
Ground Wire0.42 Ohm/1000ft (1.4 Ohm/km)75 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension3408.3 lbs (1546.0 kg)
Bulk Cable Weight1177 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.5.625 in (142.9 mm)
Installation Min.6.75 in (171 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 310, TC-ER, THWN-2
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.484 Revision Date: 04-08-2026

Resources

Related tray & tc cable