Belden Store
Belden28150AC

Product Number: 28150AC

TC VN/PVC, 3+G C #8+10 Str BC, PVC-NYL Ins M4, LCS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 8+10AWG (Class B) Bare Copper, PVC-NYL Insulation M4 Color Code, Longitudinal Corrugated Copper Tape, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

28150AC is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
28150AC 0105000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.80 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA

Construction Details

Overall Cable Diameter (Nominal)0.696 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)38 AWG7x16BC - Bare Copper
Ground Wire110 AWG7x18BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.038 in (0.97 mm)0.218 in mmBlack and Numbered
No Insulation

Outer Shield

Shield TypeCorrugated Tape
MaterialBare Copper (BC)
Coverage100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.696 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR0.94 Ohm/1000ft (3.1 Ohm/km)

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.64 Ohm/1000ft55 Amps per Conductor at 30oC
Ground Wire1.08 Ohm/1000ft (3.54 Ohm/km)40 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension928.8 lbs (421.3 kg)
Bulk Cable Weight324 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C To +90°C

Bend Radius

Stationary Min.8.352 in (212.1 mm)
Installation Min.8.352 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.80 Revision Date: 02-20-2026

Resources

Related tray & tc cable