TC-ER VN/PVC, 4 C #10 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
UL Type TC (1277) PVC-Nylon/PVC, 4 Conductor 10AWG (7x18) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
- Availability
- Global
- Status
- Active
- Orderable items
- 3
Part numbers
28140AS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | Putup Type | Length | Order |
|---|---|---|---|---|
| 28140AS 0105000 | Black | Reel | 5,000 ft | Order online |
| 28140AS01010000 | Black | Reel | 10,000 ft | Order online |
| 28140AS01020000 | Black | Reel | 20,000 ft | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.75 Revision Date: 04-08-2026 |
| Footnote | C - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN. |
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.500 in (12.7 mm) |
|---|
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 4 |
| Size | 10 AWG |
| Stranding | 7x18 |
| Material | BC - Bare Copper |
Insulation
| Element | Conductor(s) |
|---|---|
| Material | PVC/Nylon - Polyvinyl Chloride + Nylon |
| Nom. Thickness | 0.028 in (0.71 mm) |
| Nom. Insulation Diameter | 0.166 in mm |
| Color Code | Black, Red, Blue, Orange |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.047 in (1.2 mm) |
| Nom. Diameter | 0.500 in (12.7 mm) |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | 1.06 Ohm/1000ft |
|---|---|
| Max. Current | 32 Amps per conductor at 30°C |
Voltage
| UL Voltage Rating | 600 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 587.2 lbs (266.3 kg) |
|---|---|
| Bulk Cable Weight | 232 lbs/1000ft |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -30°C To +90°C |
Bend Radius
| Stationary Min. | 6 in (150 mm) |
|---|---|
| Installation Min. | 6 in (150 mm) |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
|---|---|
| Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC-ER, THWN-2 |
| European Directive Compliance | EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| Plenum Number | ICEA S-73-532, S-95-658, S-61-402 |
History
| Update and Revision | Revision Number: 0.75 Revision Date: 04-08-2026 |
|---|---|
| Footnote | C - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN. |
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon