Belden Store
28140A

Product Number: 28140A

TC VN/PVC, 4 C #10 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 4 Conductor 10AWG (7x18) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

28140A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
28140A 0105000BlackReel5,000 ft612825135449C ZOrder online
28140A 01010000BlackReel10,000 ft612825135432C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.642 Revision Date: 04-08-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0551RA

Construction Details

Conductor

ElementConductor(s)
No. of Elements4
Size10
Stranding7x18
MaterialBC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.156 in (3.96 mm)
Color CodeBlack, Red, Blue, Orange

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.495 in (12.6 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR1.06 Ohm/1000ft
Max. Current32 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER)

Mechanical Characteristics

Max. Pull Tension600 lbs (270 kg)
Bulk Cable Weight156 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.1.96 in (49.8 mm)
Installation Min.2.45 in (62.2 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, THWN-2 Singles
European Directive ComplianceEU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)