Belden Store
28098A

Product Number: 28098A

TC VN/PVC, 20 C #14 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 20 Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

28098A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
28098A 0105000Reel612825330325Order online
28098A 0105000Reel612825330325Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.408 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA

Construction Details

Overall Cable Diameter (Nominal)0.726 in (18.4 mm)

Conductor

ElementConductor(s)
No. of Elements20
Size14 AWG
Stranding7x22
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Nom. Insulation Diameter0.113 in mm
Color CodeBlack, Red, Blue, Orange, Yellow, Brown, Red/Black, Blue/Black, Orange/Black, Yellow/Black, Brown/Black, Black/Red, Blue/Red, Orange/Red, Yellow/Red, Brown/Red, Black/Blue, Red/Blue, Orange/Blue, Yellow/Blue

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.726 in (18.4 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR2.7 Ohm/1000ft
Max. Current12.5 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension874 lbs (396 kg)
Bulk Cable Weight408 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C To +90°C

Bend Radius

Stationary Min.2.904 in (73.76 mm)
Installation Min.3.63 in (92.2 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.408 Revision Date: 02-20-2026

Resources