Belden Store
28085AS

Product Number: 28085AS

TC VN/PVC, 7 C #14 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 7 Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

28085AS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
28085AS 0105000BlackReel5,000 ft612825135166C ZOrder online
28085AS01010000BlackReel10,000 ft612825135173C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.393 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0551RA

Construction Details

Overall Cable Diameter (Nominal)0.434 in (11.0 mm)

Conductor

ElementConductor(s)
No. of Elements7
Size14 AWG
Stranding7x22
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.019 in (0.48 mm)
Nom. Insulation Diameter0.112 in (2.84 mm)
Color CodeBlack, Red, Blue, Orange, Yellow, Brown, Red/Black

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type14 AWG (7x22) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.434 in (11.0 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR2.32 Ohm/1000ft (7.61 Ohm/km)

Electricals

Nom. Conductor DCR2.67 Ohm/1000ft
Max. Current17.5 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension436.8 lbs (198.1 kg)
Bulk Cable Weight169 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.5.208 in (132.3 mm)
Installation Min.5.208 in (132.3 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 310, Article 760, NPLF, TC-ER, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.393 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Resources