Belden Store
Belden27641AS

Product Number: 27641AS

TC VN/PVC, 2 C #12 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 2 Conductor 12 AWG (7x20) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
4

Ships from and sold by A5 IT.

Part numbers

27641AS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
27641AS 0105000Reel612825329701Order online
27641AS01010000Reel612825329718Order online
27641AS 0105000Reel612825329701Order online
27641AS01010000Reel612825329718Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.71 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0551RA

Construction Details

Overall Cable Diameter (Nominal)0.366 in

Conductor

ElementConductor(s)
No. of Elements2
Size12 AWG
Stranding7x20
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Nom. Insulation Diameter0.134 in mm
Color CodeBlack and Numbered

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type14 AWG (7x22) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.366 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR2.03 Ohm/1000ft (6.66 Ohm/km)

Electricals

Nom. Conductor DCR1.68 Ohm/1000ft
Max. Current30 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension228 lbs (103 kg)
Bulk Cable Weight89 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to 90°C Dry/Wet

Bend Radius

Stationary Min.4.392 in (111.6 mm)
Installation Min.4.392 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, T-29-520, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, TC-ER, NPLF, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)