Belden Store
27331AS

Product Number: 27331AS

TC VN/PVC, 3 C #16 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3 Conductor 16AWG (7x24) Bare Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

27331AS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
27331AS 0105000BlackReel5,000 ft612825133810C ZOrder online
27331AS01010000BlackReel10,000 ft612825133827C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.491 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0551RA

Construction Details

Overall Cable Diameter (Nominal)0.309 in

Conductor

ElementConductor(s)
No. of Elements3
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.020 in (0.51 mm)
Nom. Insulation Diameter0.099 in (2.5 mm)
Color CodeICEA Chart E2

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.309 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR5.47 Ohm/1000ft (17.9 Ohm/km)

Electricals

ElementConductor(s)
Nom. Conductor DCR4.2 Ohm/1000ft
Max. Current18 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension130 lbs (59 kg)
Bulk Cable Weight62 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.3.708 in (94.18 mm)
Installation Min.3.708 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, NPLF, TC
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.491 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.