Product Number: 27153A

TC VN/PVC, 3+G C #6+8 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC 90C Wet/Dry SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 6+8AWG (7x14+7x16) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC 90C Wet/Dry SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

27153A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
27153A 0105000BlackReel5,000 ft612825133315COrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.661 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA

Construction Details

Overall Cable Diameter (Nominal)0.68 in (17 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)36 AWG7x14BC - Bare Copper
Ground Wire18 AWG7x16BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.038 in (0.97 mm)0.254 in (6.45 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.68 in (17 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.42 Ohm/1000ft75 Amps per Conductor at 30oC
Ground Wire0.68 Ohm/1000ft (2.2 Ohm/km)57 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension1262.1 lbs (572.48 kg)
Bulk Cable Weight410 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -30°C to 90°C

Bend Radius

Stationary Min.2.72 in (69.1 mm)
Installation Min.3.4 in (86 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC, THWN-2
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)