Belden Store
27150A

Product Number: 27150A

TC VN/PVC, 3+G C #8+10 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 3+G Conductor 8+10AWG (7x16+7x18H) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

27150A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
27150A 0105000Reel612825133247Order online
27150A 0105000Reel612825133247Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.625 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA

Construction Details

Overall Cable Diameter (Nominal)0.595 in (15.1 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)38 AWG7x16BC - Bare Copper
Ground Wire110 AWG7x18BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.038 in (0.97 mm)0.218 in (5.54 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.595 in (15.1 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.66 Ohm/1000ft55 Amps per Conductor at 30oC
Ground Wire1.08 Ohm/1000ft (3.54 Ohm/km)42 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension792 lbs (359 kg)
Bulk Cable Weight286 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C To +75°C Wet/90°C Dry

Bend Radius

Stationary Min.2.38 in (60.5 mm)
Installation Min.2.975 in (75.57 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC, THHN, THWN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.625 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP.

Resources

Related tray & tc cable