Belden Store
Belden27149AX

Product Number: 27149AX

TC VN/PVC, 2 C #8 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 2 Conductor 8AWG (7x16) Bare Copper, PVC-NYL Insulation M4 Color Code, Black PVC Outer Jacket, 600V TC 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

27149AX is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
27149AX01010000ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.81 Revision Date: 02-20-2026

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0551RA

Construction Details

Overall Cable Diameter (Nominal)0.506 in

Conductor

ElementConductor(s)
No. of Elements2
Size8 AWG
Stranding7x16
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.032 in (0.81 mm)
Nom. Insulation Diameter0.206 in mm
Color CodeBlack and Numbered

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.506 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR0.666 Ohm/1000ft
Max. Current55 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC)

Mechanical Characteristics

Max. Pull Tension436.8 lbs (198.1 kg)
Bulk Cable Weight220 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C to 90°C Dry/Wet

Bend Radius

Stationary Min.2.024 in (51.41 mm)
Installation Min.2.53 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC, THHN, THWN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.81 Revision Date: 02-20-2026

Resources

Related tray & tc cable