Belden Store
27090A

Product Number: 27090A

TC VN/PVC, 12 C #14 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 12 Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

27090A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPut-Up TypeLengthUPCOrder
27090A 0105000BlackReel5,000 ft612825132844Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.409 Revision Date: 04-02-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Physical Characteristics (Overall)

Conductor Count12

Conductor

ElementConductor(s)
AWG14
Stranding7x22
MaterialBC - Bare Copper
No. of Conductors12

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nominal Diameter0.116 in

Color Chart

NumberColor
1Black
2Red
3Blue
4Orange
5Yellow
6Brown
7Red/Black
8Blue/Black
9Orange/Black
10Yellow/Black
11Brown/Black
12Black/Red

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.607 in
Nominal Wall Thickness0.063 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR2.52 Ohm/1000ft

Current

Max. Recommended Current [A]7.5 Amps per Conductor

Voltage

UL DescriptionUL Voltage RatingVoltage Rating [V]
TC600 V RMS (Type TC)600 V RMS (Type TC)
NPLF150 V RMS (NPLF)

Temperature Range

Wet Temp Range-30°C To +75 °C
Dry Temp Range-30°C To +90 °C

Mechanical Characteristics

Bulk Cable Weight270 lbs/1000ft
Maximum Recommended Pulling Tension655 lbs
Minimum Minor Axis Bend Radius2.43 in

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/96/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes
MII Order #39 (China RoHS)Yes

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 UL Loading
IEEE FlammabilityIEEE 1202
UL voltage rating600 V RMS (Type TC)

Plenum/Non-Plenum

Plenum (Y/N)No

Related Part Numbers

FootnoteC - CRATE REEL PUT-UP.

History

Update and RevisionRevision Number: 0.409 Revision Date: 04-02-2026

Resources

Related tray & tc cable