Belden Store
27088A

Product Number: 27088A

TC VN/PVC, 10 C #14 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

UL Type TC (1277) PVC-Nylon/PVC, 10 Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

27088A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
27088A 0105000BlackReel5,000 ft612825132820COrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.601 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP.

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC075A0791RA

Construction Details

Overall Cable Diameter (Nominal)0.590 in

Conductor

ElementConductor(s)
No. of Elements10
Size14 AWG
Stranding7x22
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
SeparatorConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.024 in (0.61 mm)
Nom. Insulation Diameter0.116 in (2.95 mm)
Color CodeBlack, Red, Blue, Orange, Yellow, Brown, Red/Black, Blue/Black, Orange/Black, Yellow/Black

Inner Shield

Shield TypeNo Shield

Outer Shield

Shield TypeNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.590 in

Electrical Characteristics

Electricals

Nom. Conductor DCR2.67 Ohm/1000ft
Max. Current12.5 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension437 lbs (198 kg)
Bulk Cable Weight229 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30°C To +75°C Wet/90°C Dry

Bend Radius

Stationary Min.2.36 in (59.9 mm)
Installation Min.2.95 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireUL1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, NPLF, TC, THHN, THWN
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.601 Revision Date: 02-20-2026
FootnoteC - CRATE REEL PUT-UP.

Resources