600V Type TC/CIC, (2) 10 AWG (7x18) BC+Grd, XLPE/PVC

Two 10 AWG stranded (7x18) bare copper conductors plus ground wire, cross-linked polyethylene insulation, PVC jacket.

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)0.477 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)210 AWG7x18BC - Bare Copper
Ground112 AWG7x20BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.174 in (4.42 mm)Black, White
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.174 in (4.42 mm)Green

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.057 in (1.4 mm)
Nom. Diameter0.477 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.04 Ohm/1000ft (3.41 Ohm/km)35 Amps per Conductor at 30oC
Ground Wire1.66 Ohm/1000ft (5.45 Ohm/km)

Voltage

Voltage Rating600 V (CSA TC)

Mechanical Characteristics

Max. Pull Tension360.4 lbs (163.5 kg)
Bulk Cable Weight157 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -40°C to 90°C
Installation-25°C To +90

Bend Radius

Stationary Min.1.908 in (48.46 mm)
Installation Min.2.385 in

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor Direct Burial, Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireFT4
AWM ComplianceC22.2#230 Type TC, C22.2#239 Type CIC
CEC / C(UL) ComplianceTC, CIC.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.125 Revision Date: 05-19-2026